WindPy Engineering Suite

NSCP 2015 / ASCE 7-16 Wind Load Analysis Tools

Building Parameters
kph
m
m
m
Fig. 207B.4-1
degrees — θ < 10° uses the flat zone table
m — used as qh reference when θ ≤ 10° (note 7)
m — horizontal projection (§207B.4.4)
m — tributary width for the overhang force
m — qp is taken at the parapet TOP (§207B.4.5)
Exempts the Fig. 207B.4-1 note 9 horizontal-shear floor
Granted by Appendix D of ASCE 7-10, which is outside NSCP §207 — you own that determination.
Getting Started

Enter the building parameters and click Calculate Wind Pressure.

This calculator follows NSCP 2015 §207B (Directional Procedure, buildings of all heights) for MWFRS wall and roof pressures — walls and roofs from Figure 207B.4-1 (printed p. 2-74), overhangs from §207B.4.4, parapets from §207B.4.5, the four design wind load cases from §207B.4.6 / Fig. 207B.4-8 and the minimum load from §207B.4.7. It computes velocity pressure, gust factor, wall pressure coefficients (windward, leeward, sidewall), flat / gable / hip / monoslope roof pressure zones, the torsional load cases and the note 9 horizontal-shear floor.